basic facilities. José García Coleto jogarcol@yahoo.es http://coleto-automatismosyautomatas.blogspot.com/ CONTENTS: INTRODUCTION - FIGURES IN THE ELECTRICAL CIRCUIT ELEMENTARY - OHM'S LAW - ACTION ON ELECTRIC circuits is ELEMENTAL. - ELECTRIC POWER CIRCUIT ELEMENTAL . - POWER. - ISSUES. - BASIC FACILITIES SCHEDULES - BASIC FACILITIES SCHEME (II) - CIRCUITS CHARACTERISTICS OF HOUSING. SCHEMES basic facilities.
1 .- simple point of light. Functional scheme
Click to view.
functional in the diagrams represent the same in the most simplified possible, we can easily see which is the operation of the assembly. Likewise are the basis for assembly of actual schemes.
simple point of light. Real scheme.
Click to view.
Once we know the functional outline the next step is to mount the installation as it would in reality.
The actual schema assembly is achieved by a methodical reading of the functional scheme, in this case would be:
a) From phase we get a driver to a fuse terminal (not shown in the actual schema)
b) the other terminal of the driver pull a fuse to a switch terminal.
c) The other terminal of the switch to a terminal to join the lamp.
d) The other terminal of the lamp's join with the neutral.
2 .- Light spot switched from two points. Functional scheme. Click to view.
Before drawing the actual schema is appropriate that we observe in the figure above the differences between a switch and a switch.
As shown the switch has three terminals that are identified with signs: c, 1 and 2.
The terminal "c" (common) will always continue with the other two terminals, the figure would give continuity to the terminal 2 but If you operate the mechanism would cease to continue with the 2 and happen to give continuity with the 1
Click to view.
Performance: 1 .-
position constraint represented the lamp would be off.
2 .- If the common triggers C1 (c) would give continuity to the terminal (1) and therefore the current may flow until the switch lighting the lamp C2.
3 .- If we start from the situation before and we activate your terminal C2 (c) would give continuity to the terminal (2) and therefore the lamp fail.
Repeat these opportunities as often as want.
This installation is typical in the bedroom, turn on the lamp to enter the room and off from the bedside table.
light point switched from two points. Real scheme. Click to view.
3 .- Light spot switched from three points. Click to view.
To make this assembly will use a new mechanism, the crossover switch.
As shown in Figure switch crossing has four terminals, so you always are giving continuity pairs. The two possible combinations are:
Position 1:
continuity 1 to 3 continued 1 to 2
Position 2:
continuity 2 to 4 3 -4
continuity
Terminals never give continuity are (1 to 4) and (2 to 3)
Click to view.
light point switched from three points. Real scheme.
This type of installation is typical of the double bedrooms, light can be controlled from the input and from each of the bedside tables.
If the number of switching points is greater than three would be achieved by inserting cross switches.
facilities discussed so far are plants belonging to the lighting circuit, some characteristics of this circuit in accordance with the Regulation for Low Tension are:
Click to view.
(5) This corresponds to an installation of two ground conductors and PVC in conduit embedded in work, according to Table 1 of ITC-BT-19. Other sections may be required for other types of cable or installation conditions.
(9) The point of light include conductor.
From the practical point of view we are interested in the four values \u200b\u200bof the columns on the right:
- Gauge circuit breaker: 10A
- Maximum number of points used per circuit: 30
- Minimum cross-section conductors:
- 1.5 mm2 diameter tube that houses the wires: 16 mm.
The table above is for a voltage of 230V between phase and neutral.
José García Coleto jogarcol@yahoo.es
http://coleto-automatismosyautomatas.blogspot.com/